Handbook

Rebuilding the Front Stoop to the Village Code

A stoop is the one piece of flatwork the building code measures closely: every riser, every tread, the landing at the door and, in Libertyville, a lower trigger for a guard than most places use. Rebuild it once, and to the right numbers.

Front steps usually come up for replacement for one of three reasons. They have settled away from the house and left a gap at the threshold. The treads have scaled and spalled after years of salt tracked up from the drive. Or the bottom riser has grown as the walk beneath it dropped, and someone has already tripped on it. In each case the temptation is to copy the old steps exactly. That is often the wrong brief.

Steps poured decades ago were built to whatever rules applied then, and sometimes to none. A rebuild is the moment to get the geometry right, because concrete steps are not something you adjust later. If your stoop is at that stage, our concrete repair page covers when a set of steps can be saved and when replacement is the honest answer.

Which code the Village is on

Libertyville adopted the 2018 International Residential Code as part of Ordinance 19-O-17 in March 2019, in force from May of that year, together with a list of local amendments. The Building Division still lists that edition on its construction codes page.

That matters because Lake County's own code, the one that applies outside the villages, moved to a newer edition this year, and a contractor who works across the county can easily carry the wrong book into the Village. We explain why the edition differs from one town to the next in our note on code editions. For steps, the practical point is simply to ask which edition your contractor is drawing to.

The dimensions that matter at a front door

The residential code treats the landing and the stair as two separate things, and both have to be right.

2018 IRC itemRequirement
Landing at an exterior door (R311.3)Required on each side; at least as wide as the door; at least 36 in. in the direction of travel
Landing slope (R311.3)No steeper than 1/4 in. per foot
Drop from threshold to landing (R311.3.1)Up to 1 1/2 in.; up to 7 3/4 in. where the door does not swing out over the landing
Stair width (R311.7.1)At least 36 in. clear
Riser height (R311.7.5.1)7 3/4 in. maximum
Tread depth (R311.7.5.2)10 in. minimum
Variation within one flightNo more than 3/8 in., risers and treads alike
Nosing (R311.7.5.3)3/4 to 1 1/4 in.; not required where treads are 11 in. or deeper
Landing at the foot of the stair (R311.7.6)Required; 36 in. deep on a straight run
Tread and landing surface (R311.7.7)No steeper than 1 unit in 48

Two lines in that table cause most of the trouble on a rebuild. The first is the landing depth. Older stoops are often a narrow ledge in front of the door, too shallow to stand on while the storm door swings. The second is the 3/8 inch tolerance. It is tight on purpose, because the foot learns the rhythm of a stair in the first two steps and stumbles on the one that breaks it. That is why a sunken walk that lengthens only the last riser is a genuine hazard, not a cosmetic one.

Handrails, and the Village's lower guard trigger

The handrail rule is straightforward: four or more risers in a flight, and a rail is required on at least one side, between 34 and 38 inches up from the nosing line.

Guards are where Libertyville departs from the book. The published code requires a guard on an open side where the walking surface is more than 30 inches above the ground below. The Village amended that figure to 18 inches. A generous stoop on a house with a raised first floor can easily sit more than a foot and a half above the lawn at its open edge, and here that means a guard, where the same stoop in a town using the unamended code might need nothing.

Guard rulePublished 2018 IRCAs amended by Libertyville
Drop that triggers a guard (R312.1.1)More than 30 in.More than 18 in.
Guard height (R312.1.2)36 in.; 34 in. along the open side of stairs

Plan the railing with the concrete, not after it. Posts anchored into fresh concrete, or sleeves set for them during the pour, are far neater than holes cored into a finished stoop.

How the Village expects a stoop to be held

This is the part of the local code most specific to concrete. Section 6-130 of the municipal code deals with exterior porches, platforms and stairs directly.

If a porch or stair carries walls or a roof, it needs a full foundation under every side, poured with the house foundation and taken to the depth the Village requires for foundations. Open steps that carry no roof may instead stand on wing walls tied back into the foundation, and then the anchoring is spelled out.

Libertyville Sec. 6-130 itemWhat it requires
Foundation depth, where one is required (6-130(a))42 in. below grade
Wing walls tied to the foundation (6-130(d))At least two 1/2 in. bars from the foundation wall into the top 4 in. of each wing wall
Platform and stairs on wing walls (6-130(d))Anchored to the foundation wall with 1/2 in. bars at 2 ft. on center or closer, into the platform or top tread
Small roofed landing (Exception 1)30 sq ft or less and no more than 6 ft in any direction may sit on approved piers below the frost line

The reasoning is the same problem the old stoop probably shows: concrete steps set loose against a house move independently of it, and the gap at the threshold is the result. Anchoring ties the two together so they move as one. On an existing house, meeting the rule means drilling into the foundation wall and setting the bars before the pour, which is work to agree up front rather than discover on the day.

Permits, and a question to ask

The Village's residential permit list has no separate line for replacing a set of steps, so we will not tell you one is or is not needed. Ask the Building Division before work starts; it is a short call, and the answer depends on what exactly is being built. A roofed porch is plainly a different matter from steps alone.

What to agree with the crew

  • The riser count and height, on paper. Measure the total rise from the finished walk to the threshold and divide it evenly. Uneven division is the most common fault in rebuilt steps.
  • The landing depth. Aim for the full depth in front of the door, not the width of the old ledge.
  • The guard and rail. Decide whether the open side crosses the Village's lower guard line, and set posts or sleeves in the pour.
  • The anchoring. Ask how the new steps will be tied to the foundation wall.
  • The walk below. If it has sunk, fix it with the steps, or the bottom riser will be wrong again within a few winters.

Steps built to these numbers stop being the part of the house everyone watches their feet on. When you are ready, describe the stoop through our repair and replacement request, with a photo from the side if you can, and the crew will come out to measure it.

Sources

  1. Village of Libertyville, Construction Codes - the adopted 2018 International Residential Code (adopted 12 March 2019, effective 1 May 2019), and the Municipal Code Chapter 6 amendments document: Ordinance 19-O-17, Sec. 6-130 on foundation depth and the anchoring of exterior platforms and stairs, and the amendment of R312.1.1 from 30 to 18 inches. Read 28 September 2026.
  2. International Code Council, 2018 International Residential Code, Chapter 3 - exterior door landings (R311.3), stair width, risers, treads, nosings, landings and walking surface (R311.7), handrails (R311.7.8) and guards (R312.1). Read 28 September 2026.
  3. Village of Libertyville, Residential Permit - the list of residential project types and their submittals. Read 28 September 2026.

Request a Quote

Get your free, on-site quote.

Tell us about your project and we'll call you back the same day to set up a free measure and price.

Get your free quote

Tell us about your project and we will call you back the same day. No obligation.

What are you looking to do?
Roughly how big?
When are you thinking?

Pricing it out is fine. We will not chase you.

What is your ZIP code?

So we can confirm you are in the service area.

Where should we send it?

Free, no-pressure quote · Serving Lake County, IL

By submitting, you agree to our Privacy Policy and Terms, and consent to be contacted by phone, text, or email about your project, including by automated means. Consent isn't a condition of purchase. Msg & data rates may apply.

Call (262) 228-5293 Text us